By Blissom · Updated 2026-10-23
Use the table for your conduit type and wire insulation. Every conductor in the raceway counts, including the equipment ground. For mixed sizes, use the conduit fill calculator. These charts show conduit fill capacity only, not allowable circuit ampacity: with more than three current-carrying conductors in a raceway, NEC 310.15(C)(1) generally requires ampacity adjustment, and equipment grounding conductors count for fill but not as current-carrying.
EMT fill chart, THHN
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 | 476 | 608 |
| #12 | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 443 |
| #10 | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 | 219 | 279 |
| #8 | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 | 126 | 161 |
| #6 | 2 | 4 | 7 | 12 | 16 | 26 | 46 | 69 | 91 | 116 |
| #4 | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 71 |
| #3 | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| #2 | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 | 40 | 51 |
| #1 | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 | 29 | 37 |
| #1/0 | 1 | 1 | 1 | 3 | 4 | 7 | 12 | 19 | 25 | 32 |
| #2/0 | — | 1 | 1 | 2 | 3 | 6 | 10 | 16 | 20 | 26 |
| #3/0 | — | 1 | 1 | 1 | 3 | 5 | 8 | 13 | 17 | 22 |
| #4/0 | — | 1 | 1 | 1 | 2 | 4 | 7 | 11 | 14 | 18 |
PVC Sch 40 fill chart, THHN
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 11 | 21 | 34 | 60 | 82 | 135 | 193 | 299 | 401 | 517 |
| #12 | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 218 | 293 | 377 |
| #10 | 5 | 9 | 15 | 27 | 37 | 62 | 89 | 137 | 184 | 238 |
| #8 | 3 | 5 | 9 | 16 | 21 | 36 | 51 | 79 | 106 | 137 |
| #6 | 1 | 4 | 6 | 11 | 15 | 26 | 37 | 57 | 77 | 99 |
| #4 | 1 | 2 | 4 | 7 | 9 | 16 | 22 | 35 | 47 | 61 |
| #3 | 1 | 1 | 3 | 6 | 8 | 13 | 19 | 30 | 40 | 51 |
| #2 | 1 | 1 | 3 | 5 | 7 | 11 | 16 | 25 | 33 | 43 |
| #1 | 1 | 1 | 1 | 3 | 5 | 8 | 12 | 18 | 25 | 32 |
| #1/0 | 1 | 1 | 1 | 3 | 4 | 7 | 10 | 15 | 21 | 27 |
| #2/0 | — | 1 | 1 | 2 | 3 | 6 | 8 | 13 | 17 | 22 |
| #3/0 | — | 1 | 1 | 1 | 3 | 5 | 7 | 11 | 14 | 18 |
| #4/0 | — | 1 | 1 | 1 | 2 | 4 | 6 | 9 | 12 | 15 |
PVC Sch 80 fill chart, THHN
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 9 | 17 | 28 | 51 | 70 | 118 | 170 | 265 | 358 | 464 |
| #12 | 6 | 12 | 20 | 37 | 51 | 86 | 124 | 193 | 261 | 338 |
| #10 | 4 | 7 | 13 | 23 | 32 | 54 | 78 | 122 | 164 | 213 |
| #8 | 2 | 4 | 7 | 13 | 18 | 31 | 45 | 70 | 95 | 123 |
| #6 | 1 | 3 | 5 | 9 | 13 | 22 | 32 | 51 | 68 | 89 |
| #4 | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 42 | 54 |
| #3 | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 26 | 35 | 46 |
| #2 | 1 | 1 | 2 | 4 | 6 | 10 | 14 | 22 | 30 | 39 |
| #1 | — | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 22 | 29 |
| #1/0 | — | 1 | 1 | 2 | 3 | 6 | 9 | 14 | 18 | 24 |
| #2/0 | — | 1 | 1 | 1 | 3 | 5 | 7 | 11 | 15 | 20 |
| #3/0 | — | 1 | 1 | 1 | 2 | 4 | 6 | 9 | 13 | 17 |
| #4/0 | — | — | 1 | 1 | 1 | 3 | 5 | 8 | 10 | 14 |
Rigid (RMC) fill chart, THHN
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 13 | 22 | 36 | 63 | 85 | 140 | 200 | 309 | 412 | 531 |
| #12 | 9 | 16 | 26 | 46 | 62 | 102 | 146 | 225 | 301 | 387 |
| #10 | 6 | 10 | 17 | 29 | 39 | 64 | 92 | 142 | 189 | 244 |
| #8 | 3 | 6 | 9 | 16 | 22 | 37 | 53 | 82 | 109 | 140 |
| #6 | 2 | 4 | 7 | 12 | 16 | 27 | 38 | 59 | 79 | 101 |
| #4 | 1 | 2 | 4 | 7 | 10 | 16 | 23 | 36 | 48 | 62 |
| #3 | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 41 | 53 |
| #2 | 1 | 1 | 3 | 5 | 7 | 11 | 17 | 26 | 34 | 44 |
| #1 | 1 | 1 | 1 | 4 | 5 | 8 | 12 | 19 | 25 | 33 |
| #1/0 | 1 | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 21 | 27 |
| #2/0 | — | 1 | 1 | 2 | 3 | 6 | 8 | 13 | 18 | 23 |
| #3/0 | — | 1 | 1 | 1 | 3 | 5 | 7 | 11 | 15 | 19 |
| #4/0 | — | 1 | 1 | 1 | 2 | 4 | 6 | 9 | 12 | 16 |
IMC fill chart, THHN
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 14 | 24 | 39 | 68 | 91 | 149 | 211 | 326 | 436 | 562 |
| #12 | 10 | 17 | 29 | 49 | 67 | 109 | 154 | 238 | 318 | 410 |
| #10 | 6 | 11 | 18 | 31 | 42 | 69 | 97 | 150 | 200 | 258 |
| #8 | 3 | 6 | 10 | 18 | 24 | 39 | 56 | 86 | 115 | 149 |
| #6 | 2 | 4 | 7 | 13 | 17 | 28 | 40 | 62 | 83 | 107 |
| #4 | 1 | 3 | 4 | 8 | 11 | 17 | 25 | 38 | 51 | 66 |
| #3 | 1 | 2 | 4 | 6 | 9 | 15 | 21 | 32 | 43 | 56 |
| #2 | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 27 | 36 | 47 |
| #1 | 1 | 1 | 2 | 4 | 5 | 9 | 13 | 20 | 27 | 35 |
| #1/0 | 1 | 1 | 1 | 3 | 4 | 8 | 11 | 17 | 23 | 29 |
| #2/0 | 1 | 1 | 1 | 3 | 4 | 6 | 9 | 14 | 19 | 24 |
| #3/0 | — | 1 | 1 | 2 | 3 | 5 | 7 | 12 | 16 | 20 |
| #4/0 | — | 1 | 1 | 1 | 2 | 4 | 6 | 9 | 13 | 17 |
Flex (FMC) fill chart, THHN
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 13 | 22 | 33 | 52 | 76 | 135 | 202 | 291 | 396 | 518 |
| #12 | 9 | 16 | 24 | 38 | 56 | 98 | 147 | 212 | 289 | 378 |
| #10 | 6 | 10 | 15 | 24 | 35 | 62 | 93 | 134 | 182 | 238 |
| #8 | 3 | 6 | 9 | 14 | 20 | 35 | 53 | 77 | 105 | 137 |
| #6 | 2 | 4 | 6 | 10 | 14 | 25 | 38 | 55 | 76 | 99 |
| #4 | 1 | 2 | 4 | 6 | 9 | 16 | 24 | 34 | 46 | 61 |
| #3 | 1 | 1 | 3 | 5 | 7 | 13 | 20 | 29 | 39 | 51 |
| #2 | 1 | 1 | 3 | 4 | 6 | 11 | 17 | 24 | 33 | 43 |
| #1 | 1 | 1 | 1 | 3 | 4 | 8 | 12 | 18 | 24 | 32 |
| #1/0 | 1 | 1 | 1 | 2 | 4 | 7 | 10 | 15 | 20 | 27 |
| #2/0 | — | 1 | 1 | 1 | 3 | 6 | 9 | 12 | 17 | 22 |
| #3/0 | — | 1 | 1 | 1 | 2 | 5 | 7 | 10 | 14 | 18 |
| #4/0 | — | 1 | 1 | 1 | 1 | 4 | 6 | 8 | 12 | 15 |
EMT fill chart, XHHW
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 8 | 15 | 25 | 43 | 58 | 96 | 168 | 254 | 332 | 424 |
| #12 | 6 | 11 | 19 | 33 | 45 | 74 | 129 | 195 | 255 | 326 |
| #10 | 5 | 8 | 14 | 24 | 33 | 55 | 96 | 145 | 190 | 243 |
| #8 | 2 | 5 | 8 | 13 | 18 | 30 | 53 | 81 | 105 | 135 |
| #6 | 1 | 3 | 6 | 10 | 14 | 22 | 39 | 60 | 78 | 100 |
| #4 | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 72 |
| #3 | 1 | 1 | 3 | 6 | 8 | 14 | 24 | 36 | 48 | 61 |
| #2 | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 31 | 40 | 51 |
| #1 | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 23 | 30 | 38 |
| #1/0 | 1 | 1 | 1 | 3 | 4 | 7 | 13 | 19 | 25 | 32 |
| #2/0 | — | 1 | 1 | 2 | 3 | 6 | 10 | 16 | 21 | 27 |
| #3/0 | — | 1 | 1 | 1 | 3 | 5 | 9 | 13 | 17 | 22 |
| #4/0 | — | 1 | 1 | 1 | 2 | 4 | 7 | 11 | 14 | 18 |
EMT fill chart, THW
| Wire | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 6 | 10 | 16 | 28 | 39 | 64 | 112 | 169 | 221 | 282 |
| #12 | 4 | 8 | 13 | 23 | 31 | 51 | 90 | 136 | 177 | 227 |
| #10 | 3 | 6 | 10 | 18 | 24 | 40 | 70 | 106 | 138 | 177 |
| #8 | 1 | 4 | 6 | 10 | 14 | 24 | 42 | 63 | 83 | 106 |
| #6 | 1 | 3 | 4 | 8 | 11 | 18 | 32 | 48 | 63 | 81 |
| #4 | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| #3 | 1 | 1 | 3 | 5 | 7 | 12 | 20 | 31 | 40 | 52 |
| #2 | 1 | 1 | 2 | 4 | 6 | 10 | 17 | 26 | 34 | 44 |
| #1 | 1 | 1 | 1 | 3 | 4 | 7 | 12 | 18 | 24 | 31 |
| #1/0 | — | 1 | 1 | 2 | 3 | 6 | 10 | 16 | 20 | 26 |
| #2/0 | — | 1 | 1 | 1 | 3 | 5 | 9 | 13 | 17 | 22 |
| #3/0 | — | 1 | 1 | 1 | 2 | 4 | 7 | 11 | 15 | 19 |
| #4/0 | — | — | 1 | 1 | 1 | 3 | 6 | 9 | 12 | 16 |
Worked example: four #10 and three #12 THHN
- Conductor area: 4 × 0.0211 + 3 × 0.0133 = 0.1243 in².
- 1/2" EMT allows 40% of 0.304 in² = 0.1216 in²: too full, by a small margin.
- 3/4" EMT allows 0.2132 in², so the same seven conductors use 58% of what is allowed. Use 3/4".
For a single wire size, read the count straight from the tables below; mixed sizes always need the area math.
Raceway internal areas (NEC Chapter 9, Table 4)
| Trade size | EMT | IMC | Rigid (RMC) | PVC Sch 40 | PVC Sch 80 | Flex (FMC) | ENT |
|---|---|---|---|---|---|---|---|
| 3/8" | — | — | — | — | — | 0.116 | — |
| 1/2" | 0.304 | 0.342 | 0.314 | 0.285 | 0.217 | 0.317 | 0.285 |
| 3/4" | 0.533 | 0.586 | 0.549 | 0.508 | 0.409 | 0.533 | 0.508 |
| 1" | 0.864 | 0.959 | 0.887 | 0.832 | 0.688 | 0.817 | 0.832 |
| 1-1/4" | 1.496 | 1.647 | 1.526 | 1.453 | 1.237 | 1.277 | 1.453 |
| 1-1/2" | 2.036 | 2.225 | 2.071 | 1.986 | 1.711 | 1.858 | 1.986 |
| 2" | 3.356 | 3.630 | 3.408 | 3.291 | 2.874 | 3.269 | 3.291 |
| 2-1/2" | 5.858 | 5.135 | 4.866 | 4.695 | 4.119 | 4.909 | — |
| 3" | 8.846 | 7.922 | 7.499 | 7.268 | 6.442 | 7.069 | — |
| 3-1/2" | 11.545 | 10.584 | 10.010 | 9.737 | 8.688 | 9.621 | — |
| 4" | 14.753 | 13.631 | 12.882 | 12.554 | 11.258 | 12.566 | — |
Conductor areas (NEC Chapter 9, Table 5)
| Size | THHN / THWN-2 | XHHW-2 | THW / THHW |
|---|---|---|---|
| #14 | 0.0097 | 0.0139 | 0.0139 |
| #12 | 0.0133 | 0.0181 | 0.0181 |
| #10 | 0.0211 | 0.0243 | 0.0243 |
| #8 | 0.0366 | 0.0437 | 0.0437 |
| #6 | 0.0507 | 0.0590 | 0.0726 |
| #4 | 0.0824 | 0.0814 | 0.0973 |
| #3 | 0.0973 | 0.0962 | 0.1134 |
| #2 | 0.1158 | 0.1146 | 0.1333 |
| #1 | 0.1562 | 0.1534 | 0.1901 |
| #1/0 | 0.1855 | 0.1825 | 0.2223 |
| #2/0 | 0.2223 | 0.2190 | 0.2624 |
| #3/0 | 0.2679 | 0.2642 | 0.3117 |
| #4/0 | 0.3237 | 0.3197 | 0.3718 |
| 250 kcmil | 0.3970 | 0.3904 | 0.4596 |
| 300 kcmil | 0.4608 | 0.4536 | 0.5281 |
| 350 kcmil | 0.5242 | 0.5166 | 0.5958 |
| 400 kcmil | 0.5863 | 0.5782 | 0.6619 |
| 500 kcmil | 0.7073 | 0.6984 | 0.7901 |
| 600 kcmil | 0.8676 | 0.8709 | 0.9729 |
| 750 kcmil | 1.0496 | 1.0532 | 1.1652 |
Dimensional data per NEC 2023, Chapter 9. The THW area column reproduces NEC Chapter 9, Table 5. The THW counts follow the conservative published Annex C (Table C.1) counts, which for #14 to #8 are lower than a direct calculation from those Table 5 dimensions; the conduit fill calculator uses the same conservative basis. Always follow the edition your jurisdiction has adopted.
Sources: NEC 2023: Chapter 9, Tables 1, 4 and 5, Note 7, and Annex C; Conductor areas for THHN/THWN, XHHW and THW from Chapter 9, Table 5. Method.
Questions electricians ask
How many 10 AWG THHN wires fit in 3/4 EMT?
Ten #10 THHN conductors fit in 3/4" EMT. In 1/2" EMT it is 5, and in 1" EMT it is 16.
How many wires can go in 1/2 PVC?
In 1/2" PVC Schedule 40, 8 #12 THHN or 11 #14 THHN. Schedule 80 has thicker walls and holds fewer: 6 #12 or 9 #14.
Do these tables include the ground wire?
Yes, count the ground as one of the wires. The tables assume every conductor is the same size and insulation; for a mix, use the conduit fill calculator.

Fill charts offline, next to your bends