How Many Wires in 1-1/4" EMT?

By fill, 1-1/4" EMT holds 45 #12 THHN, 28 #10 or 6 #3. Its usual job is a feeder: a 100 A copper set of three #3 and a #8 ground fills only 22.0% of it.

By Blissom · Updated 2026-11-04

Feeder fill and bends, offlineConduit Bending Calculator for Android · $7.99 one time · offline · no ads
Get the app

Feeder sets in 1-1/4"

Feeders are where 1-1/4" earns its place. Below, two copper THHN sets sized from the 75 °C column. At 100 A and under that requires equipment marked for 75 °C terminations (110.14(C)(1)(a)); most current panelboards are.

Feeder sets in 1-1/4" EMT
FeederConductorsFillCountedAmpacity after adjustment
100 A, 120/240 V single-phase3 × #3 + 1 × #822.0%2100 A OK
60 A, 208Y/120 V three-phase4 × #6 + 1 × #1015.0%460 A OK

The 100 A set has two current-carrying conductors; the single-phase neutral only carries the imbalance. Grounds follow Table 250.122: #8 for 100 A, #10 for 60 A.

For the three-phase set the neutral is counted, as it would be with mostly nonlinear load. That takes it to four, factor 80%. #6 THHN drops to 60 A, which still matches the 60 A breaker. One more counted conductor in the same pipe would not change the band, but a second feeder would.

Fill counts, every wire size

1-1/4" EMT: 1.496 in² internal area, 40% usable with three or more conductors.

Most same-size conductors in 1-1/4" EMT
WireTHHN / THWN-2XHHW-2THW
#14614328
#12453323
#10282418
#8161310
#612108
#4776
#3665
#2554
#1443
#1/0332
#2/0221
#3/0111
#4/0111
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil111
600 kcmil111

Note 7 rounding applied. From 3/0 THHN up only one fits, under the 53% single-conductor limit. THW uses Annex C's larger dimensions.

Branch circuits: the same ceiling

A bigger pipe does not change how many branch conductors may share it. The bands for small wire are fixed by 310.15(C)(1):

1-1/4" EMT: fill count against the derating ceiling (THHN copper)
Wire and breakerFits by fillCurrent-carrying limitWhat stops you first
#14 on 15 A619Derating
#12 on 20 A459Derating
#10 on 20 A2820Derating
#10 on 30 A286Derating

The band-by-band derating table (80%, 70%, 50% and lower) is the same for every pipe size; it is on the 3/4" EMT page. The fill count includes one ground, which never counts toward the current-carrying limit.

So with #12 on 20 A you get 4 circuits with their own neutrals or 8 on 120/240 V shared neutrals. Most of the 45-wire fill goes unused. #10 on 20 A gets you 10 or 18 instead.

Grounds never count for derating (310.15(F)). Results may not exceed the 60 °C termination rating of 100 A and smaller equipment unless it is marked for 75 °C.

Example: four three-phase sets

Twelve 20 A, 120 V circuits on four 208Y/120 V multiwire sets: three phases and one neutral per set, plus a ground. With linear load the neutrals are not counted, leaving twelve.

Four 208Y/120 V multiwire sets on #12
ConductorsArea each (in²)Subtotal (in²)
12 × #12 THHN (phase conductors)0.01330.1596
4 × #12 THHN (neutrals)0.01330.0532
1 × #12 THHN (ground)0.01330.0133
Total, 17 conductors0.2261
Allowed: 40% of 1.496 in²0.5984

Fill is only 15.1%. Derating is the problem: twelve at 50% gives #12 15 A, below the 20 A breaker.

The same sets pulled in #10
ConductorsArea each (in²)Subtotal (in²)
12 × #10 THHN (phase conductors)0.02110.2532
4 × #10 THHN (neutrals)0.02110.0844
1 × #10 THHN (ground)0.02110.0211
Total, 17 conductors0.3587
Allowed: 40% of 1.496 in²0.5984

In #10 the fill rises to 24.0% and each conductor holds 20 A. If the load is mostly nonlinear and the neutrals count, that makes 16, still in the 50% band and still 20 A. The other route is two raceways of two sets each.

Stepping up or splitting

  • Feeder plus branch circuits in one pipe: every counted conductor of both shares the same factor. A 100 A feeder with four branch conductors alongside is six counted, and #3 at 80% is 92 A, under 100 A.
  • A larger feeder: 125 A on three #1 copper and a #6 ground fills 1-1/4" to 34.7%. Legal, but a 1-1/2" EMT pulls far easier.
  • Long runs with 360° of bends: large conductors take real force to pull. Add a pull point rather than counting on spare fill.

Check your own mix with the conduit fill calculator. NEC 2023 values; verify against the edition your inspector enforces. Hot rooftops add a 310.15(B) temperature correction.

Sources: NEC 2023: Chapter 9, Tables 1, 4 and 5 with Note 7 (fill); 310.15(C)(1) (adjustment for more than three current-carrying conductors), 310.15(E) and (F) (neutrals and grounds), Table 310.16, 240.4(D) and 110.14(C). Method.

Questions electricians ask

How many wires can go in 1-1/4 EMT?

45 #12 THHN, 61 #14, 28 #10, 6 #3 or 4 #1, all one size and including any insulated ground.

Will a 100 amp feeder fit in 1-1/4 EMT?

Yes. Three #3 THHN copper and a #8 ground use 22.0% of 1-1/4" EMT, well under 40%. Even 1" EMT passes at 38.0%, so 1-1/4" is about an easier pull.

How many 20 amp circuits fit in 1-1/4 conduit?

Derating, not the pipe, sets it. #12 THHN on 20 A tops out at 9 current-carrying conductors in any raceway. Pulling #10 for the same circuits raises that to 20 in 1-1/4".

Is the feeder neutral a current-carrying conductor?

On a 120/240 V single-phase feeder it normally is not counted. On a 208Y/120 V four-wire feeder whose load is mostly nonlinear, such as electronic equipment or LED drivers, it is counted (310.15(E)).

Conduit Bending Calculator app screen

Feeder fill and bends, offline

  • Conduit fill for feeder sets with any ground size
  • Smallest trade size that passes, per raceway type
  • Bending marks for 1-1/4" offsets and 90s
  • Box fill for the junctions too

Android only. There is no iPhone version yet; the free calculators on this site work on any phone.